CASE STUDIES

(One Hundred Questions on Waterproofing) The ceiling of the #86th-floor elevator room has experienced a leak phenomenon; given that it is above a water tank, what are the key aspects of the concept that should be considered when repairing the leak?

A: Generally, if the ceiling of the elevator room in the top floor of a residential building experiences a leak, because the water storage tank is located above it, the first thought is that it is probably caused by a water tank leak; however, it must be noted that the water tank is located in the basement of the building.

(One hundred questions on waterproofing) What is the most common mistake in the construction process when waterproofing a #84new construction site pond? Is it suitable to use PU, EPOXY or FRP construction?

Answer: (i) In the process of waterproofing the tank, the most common mistake made on construction sites is to first paint the base and then apply the waterproofing coating. The reason is that since tanks are generally prone to leakage, it is necessary to first seal the base before applying the coating.

(One Hundred Questions on Waterproofing) #83: In some cases, the waterproof coating is only applied by brushing with seven-millimeter quartz powder or by buying some waterproof agent at a hardware store; there is no leakage phenomenon. On the other hand, some construction sites use expensive imported materials from Europe and the United States, but they often leak, and repeated repairs are ineffective. Why is that?

Answer: The key lies in the structure of the tank; as in question 83, ninety percent of the water leakage is due to four major defects in the structure; if these defects are properly addressed, a simple 1:2 countermeasure can be applied.

(One Hundred Questions on Waterproofing) #81: How does waterproofing in bathrooms and toilets in newly constructed construction sites work? If (a) polyurethane (PU) is used, what is its functional performance? After construction, there is often a phenomenon of residual adhesion (not fully cured); how can this be prevented? (b) Rubberized asphalt (RA) is used; what are its advantages and disadvantages? (One Hundred Questions on Waterproofing) #81

Answer: (i) If PU construction is adopted, the waterproof performance of the RC wall remains acceptable; the only drawback is that it cannot be painted or primed; however, for the brickwork part, it is very difficult to completely seal the surface.

(One hundred questions on waterproofing) #79: How should the bathrooms and toilets in newly built construction sites be waterproofed? Which series of waterproof materials is best? Are there any blind spots that need special reinforcement?

A: (i) According to the waterproofing standards of the Japan National Association of Architects’ JASS 8, it is recommended to use a water-based composite waterproofing material (also known as the “elastic” waterproofing material commonly used in the market).

(One hundred questions about waterproofing) There is often a white coating (wall cancer) on the wall #77near the bathroom. Why does it form? If construction is not carried out from within the bathroom, what are the feasibility issues if construction is carried out from the outside wall?

Answer: (i) The water in the bathroom is heavy, while the water outside the bathroom is light. The water in the bathroom is acidic because it combines with the carbon dioxide and carbon monoxide in the air to form acidic water. These acids

(One Hundred Questions About Waterproofing) After the introduction of the #75-thread method for injecting PU foam, what is the reliability of the leak repair using this commonly used method? How reliable is the use of transparent water-repellent agent to repair window frames?

Answer: (i) Although this method of construction has the advantages of being quick and low-polluting, the actual results have the following blind spots: (1) The construction workers must possess proficient skills and wisdom;

(One Hundred Questions on Waterproofing) #70Generally, new construction sites will install waterproofed groove for windows and doors. However, contractors are strictly required to apply waterproof agent during construction. Why is there still a frequent occurrence of water leakage? How can it be prevented?

Answer: (i) The author believes that the problem of waterproofed window and door joints is a very important aspect of the construction process (have you noticed how many construction sites are flooded with rainwater after a typhoon or continuous heavy rain?).

(One hundred questions about waterproofing) Question #68: Some people say that the expense of cladding the exterior walls is too much to bear; construction from the outside is also very extensive; why not just install tiles indoors to completely solve the problem? Is this a correct view? If it is not possible to do the cladding from the outside, can it be done from the inside?

Answer: (1) Of course, that is incorrect! This kind of backward construction that ignores the root cause of the problem while ignoring the symptoms is ultimately a waste of resources and a waste of labor. While it may have good results in the short term, as long as it is carried out over a long period of time, it will inevitably lead to even greater problems.

(One Hundred Questions on Waterproofing) Old-style apartments located on the #67th floor or below often have spider-web-like cracks in the exterior walls, causing indoor water seepage and wall cancer. How should waterproofing be repaired? After waterproofing is completed, the wall cancer problem still persists after the interior is repainted. How can it be resolved?

Answer: (i) The exterior structures of older apartments below the fifth floor are mostly made of reinforced brick construction, and the surfaces are mostly waterproofed with seven-inch stone powder or cement paint; if the mortar quality is poor or there are other external

(One Hundred Questions on Waterproofing) #65 is limited by the building coverage ratio and the width of the alley; the exterior wall must be retracted into a sloped structure. If the exterior wall structure is completely remodeled, why is it particularly easy to leak water? How can it be prevented?

A: As shown in Figures A and B, after the renovation, due to the poor bond between the new and old concrete, it is particularly easy for leakage to occur at the joint area. This is an unavoidable defect that must be prevented beforehand. Preventing leakage

(One Hundred Questions on Waterproofing) How can we prevent leakage of water from indirect seams and shear stress cracks in exterior walls during construction of #64new projects? What are the construction standards for this?

Answer: It is recommended that construction companies separately bid for waterproofing for the external wall joints and the shear cracks near the windows before painting the exterior wall. This is because the cost of waterproofing beforehand is definitely much lower than the cost of fixing them afterwards.

(One Hundred Questions on Waterproofing) In the open space courtyard in the #58th floor, water leakage has occurred due to cracking in the floor slab. If we need to repair and renovate the water leakage on the courtyard, it would be too much trouble. Is it possible to repair the water leakage directly from the ceiling in the ground floor? What are the various methods of repair?

A: The courtyard leaks due to cracks in the construction of the ceiling from the basement; if the construction method is correct and the techniques are proficient, the chance of stopping the leakage can be as high as over 70%. Generally, there are only a few methods to follow: